How Many Devices Can Be on a NAC Circuit?

There is no fixed number. A NAC carries as many appliances as two limits allow. Their combined alarm current, taken from each appliance's data sheet at its candela and tone setting, has to stay within the circuit's rated output in the panel or power-supply manual. And the last appliance has to stay inside its listed voltage window once voltage drop is counted. Some appliance instructions add a count cap of their own, so read those as well.

The two limits that set the count

  1. Current. Add up the alarm current of every appliance on the circuit at the settings you chose. The total must stay at or below the NAC's rated output. Fire-Lite's MS-9200UDLS manual, §2.5, rates each of its NACs at 2.5 A. Its specifications list that 2.5 A for special application appliances and 250 mA for regulated output, so the appliance type matters too.
  2. Voltage. Alarm current flowing out and back through the wire drops voltage along the run. The last appliance has to see at least the minimum of its listed window with every appliance drawing alarm current. System Sensor's L-Series wall appliance instructions give 16 to 33 VDC for 24 V nominal use, as one manufacturer example.

System Sensor's instructions name both checks in their system design section: the total draw must not exceed what the panel supply can deliver, and the last device must run within its rated voltage.

Two more checks sit on top of those. First, the panel total. The same Fire-Lite manual caps total alarm current for all external devices at 6.0 A (§2.5), and its Figure 1.1 shows 3.0 A when only the standard transformer is installed. Four NACs at 2.5 A each would be 10 A, so on that panel the circuits can't all be loaded to their rating at once. Second, the count cap. The L-Series instructions allow no more than 69 strobes on a single NAC in 24 V applications, a ceiling for that product line that applies whatever the current and voltage checks say.

A worked example with invented numbers

All values here are invented for practice. They don't come from any product or from NFPA 72, so take the real figures from your panel and appliance manuals.

  • NAC rated output: 2.0 A, a stated example rating.
  • Appliances: 12 strobes, each drawing 0.150 A at its chosen candela setting at the low end of its voltage window.
  • Wire: 14 AWG solid copper, 200 ft one way. The resistance is 3.0713 Ω per 1,000 ft per conductor, from the copper model our calculator uses.
  • Voltage at the NAC terminals in the battery condition being checked: 20.4 V.
  • Appliance minimum: 16.0 V.

Step 1, current. 12 × 0.150 = 1.800 A. That's within the 2.0 A rating with 0.200 A to spare.

Step 2, voltage drop. Loop resistance is 2 × 200 × 3.0713 ÷ 1,000 = 1.2285 Ω. The drop is 1.800 × 1.2285 = 2.211 V, so the last strobe sees 20.4 − 2.211 = 18.189 V. That clears the 16.0 V minimum by 2.189 V. Both limits pass, so 12 strobes fit on this circuit.

Step 3, where voltage takes over. At this load the run can reach 1,000 × (20.4 − 16.0) ÷ (2 × 1.800 × 3.0713) ≈ 398 ft one way before the last strobe falls below 16.0 V. Past that length, voltage sets the count, not the current rating.

Run your own circuit in the fire alarm voltage drop calculator. Choose "Sum a device list", enter each appliance group with its quantity and current, and it totals the load and checks the last appliance against your minimum. The voltage drop formula guide shows why both conductors count and how to work a segment-by-segment check when the appliances are spread along the run.

Try one question

Question 1 of the free 10-question check on NICET FA II. No signup. About 14 minutes. Most checks include a calculation question, with a calculator on the page. Your progress saves in this browser for 24 hours, so you can stop and finish later. Then ask Strobe, the AI study assistant, why the answer is right and the others are wrong.

Question 1 of 10 · free checkUntimed

Submittal Preparation and System Layout

Which shop drawing best shows how panels, power supplies and circuits connect between floors?

Press A-D or 1-4 to choose an answer while this question is on screen.

Choose an answer to begin

Why a higher candela setting cuts the count

A strobe draws more current at a higher candela setting. In System Sensor's L-Series table for wall strobes at 16 to 33 VDC, the listed draw rises from 63 mA at 30 cd to 222 mA at 185 cd, more than three times as much. Horn strobes add tone and volume settings, and the instructions list a different draw for each combination.

Go back to the invented example and set all 12 strobes to a setting that draws 0.220 A. The total becomes 12 × 0.220 = 2.640 A, over the 2.0 A rating, even though the voltage check alone would still pass on this run. Only 9 fit: 9 × 0.220 = 1.980 A, while 10 would need 2.200 A. With 9 the drop is 1.980 × 1.2285 = 2.432 V, leaving 17.968 V at the last strobe.

The candela setting comes from the room and the layout, so don't turn it down to squeeze more strobes onto a circuit. Add a circuit instead.

How sync modules and booster power supplies change it

Sync. Synchronized strobes need a sync source. System Sensor lists three for L-Series: a power supply that generates its sync pulses, a panel NAC output set to its protocol, or its MDL3 module. Adding the MDL3 narrows the L-Series window to 16.5 to 33 V at 24 V nominal, so the last appliance has 0.5 V less to lose to the wire. Fire-Lite covers its panel's synchronized NAC operation in §4.17 of the manual.

Boosters. A booster power supply drives appliances from its own outputs. Fire-Lite's manual, §2.5, says its NACs can be expanded with FCPS Series field charger/power supplies. Appliances moved onto a booster circuit count against that supply's rating in its own manual, not the panel NAC's, and each booster circuit gets its own voltage drop check.

Batteries. Every amp of alarm current also lands on the standby batteries. Fire-Lite's §7.3 runs the alarm load through both the panel supply check and the battery load, so size the bank with the fire alarm battery calculator after you settle the appliance count.

A design margin is company practice, not an NFPA rule

Some companies keep part of each NAC's rating in reserve, so an added appliance or a changed setting later doesn't push the circuit over. How much to hold back is a company design practice, not an NFPA rule, so follow your company's standard or the engineer of record.

As an invented illustration, a 20% reserve on the 2.0 A example leaves 1.6 A to use. The 12 strobes at 1.800 A no longer fit. Ten do at 1.500 A, and 11 would need 1.650 A.

Practice it for Level II

Circuit loading questions reward the same two-step habit: total the current, then check the last appliance. Take the free 10-question Level II check. You get a score by domain and your weakest one named, with no signup or card, so you know which topics to fix first. For the supervision and wiring side of the same circuit, read what a NAC circuit is.

FAQ

Is there a maximum number of strobes on a NAC?

Not one number for every NAC. The count is set by the circuit's rated output, each strobe's draw at its setting and the voltage left at the last strobe. Some manufacturers add a cap as well: System Sensor's L-Series instructions allow no more than 69 strobes on one NAC at 24 V. Check the instructions for the appliances you use.

Does candela setting change how many devices fit?

Yes. A higher candela setting draws more current per strobe, so fewer fit under the same rating, and the larger total also raises voltage drop. In the invented example above, 12 strobes at 0.150 A fit a 2.0 A NAC, but only 9 fit at 0.220 A.

How do you check the last device's voltage?

Multiply the total alarm current by the resistance of both conductors over the run, then subtract that drop from the voltage at the NAC terminals in the battery condition you're checking. The result must stay at or above the appliance's listed minimum. The fire alarm voltage drop calculator does the arithmetic for a device list.

Sources

  • MS-9200UDLS Series Manual, 52750 Rev M, Fire-Lite, NAC specifications, Figure 1.1, §§2.5, 4.17 and 7.3. Checked 21 Nov 2026; per-NAC and panel alarm current, FCPS expansion, synchronized NAC operation and system current load.
  • L-Series wall appliance instructions, I56-5845-002, System Sensor, pp. 1 to 3. Checked 21 Nov 2026; system design checks, voltage windows with and without the MDL3, sync options, the 69-strobe limit and strobe current by candela (Table 3).
  • Alarm Ladder voltage drop calculator, Alarm Ladder. Checked 21 Nov 2026; the 14 AWG solid resistance and the example results were run through its calculation model.

Alarm Ladder editorial team

Your next step

Ready to see where you stand on NICET FA II?

Free, untimed and scored by domain. No signup. About 14 minutes. Most checks include a calculation question, with a calculator on the page. Your progress saves in this browser for 24 hours, so you can stop and finish later.

Free 10-question check

Level II course. Lessons, timed practice exams and a plan around your exam date.

Get Level II course · $149