Fire alarm voltage drop calculator (NAC circuits)

Estimate the cable voltage loss on a two-wire notification appliance circuit. The default method places all load at the end of the run, a conservative estimate for the same total current on a single radial circuit.

Draft Pending expert review.

Download your current inputs, device list and calculated results as a free CSV spreadsheet for Excel, Google Sheets or Numbers. Use the printable worksheet to print or save as PDF from your browser, with the draft warning and resistance source included.

Drafted by the TrueGrade Prep editorial team. Sources checked 17 October 2026.

Exports use your current inputs and results. Check the draft against your project's specs and the AHJ.

Circuit inputs

Results update as you type. Use listed maximum alarm current for the selected device settings and supply waveform. 1 mA = 0.001 A.

24 V is a nominal starting value. Enter available NAC terminal voltage for the operating condition being checked.

16 V is an editable example, not a universal requirement. For mixed devices, use the highest listed minimum.

20.4 V is a common design assumption that you must confirm. Use the available NAC terminal voltage at the chosen end-of-discharge condition, allowing for panel and power-supply losses. Raw battery voltage may overstate what reaches the circuit.

Requires equal-current devices at L/N, 2L/N, …, L from the source. Mixed currents or unequal spacing need a segment-by-segment calculation.

Tool ranges: 0–100,000 ft (0–30,480 m), 0–100 A, voltages above 0 up to 100 V, and up to 10,000 devices in 100 groups. These are input limits, not equipment ratings.

Calculated results

Total load: 1.5 A. Loop resistance: 1.843 Ω (outgoing plus return).

Using 3.071 Ω/1,000 ft per conductor at 75 °C. Pass/fail uses unrounded values; displays are rounded.

Source check: 24 V

All load at the end (conservative)

PASS against the entered minimum only.

Voltage drop
2.764 V (11.517% of 24 V)
Voltage at last device
21.236 V
Maximum length for this load
868.255 ft one way

Battery-condition check is off. A nominal-voltage pass does not establish performance at the end of discharge.

Fire alarm voltage drop calculator (NAC circuits)

Check inputs: Prepare this worksheet using the Print command.

How the calculation works

Let L be one-way length in feet, r the resistance of one conductor in Ω per 1,000 ft at 75 °C, I the total alarm load in amperes, Vₛ the voltage available at the circuit source, and Vₘᵢₙ the device minimum from its listing. Convert meters to feet using L(ft) = L(m) ÷ 0.3048.

  • Loop resistance: Rₗₒₒₚ = 2 × L × r ÷ 1,000.
  • Cable voltage drop: ΔV = I × Rₗₒₒₚ.
  • Drop percentage: 100 × ΔV ÷ Vₛ.
  • Voltage at the last device: Vₗₐₛₜ = Vₛ − ΔV.
  • Pass for the entered minimum: Vₗₐₛₜ ≥ Vₘᵢₙ.
  • Maximum one-way length: Lₘₐₓ = 1,000 × (Vₛ − Vₘᵢₙ) ÷ (2 × I × r), for I > 0 and Vₛ ≥ Vₘᵢₙ.

These equations apply Ohm's law (Fluke, “What is Ohm's Law?”) to the outgoing and return conductors. If the source is already below the device minimum, no length passes. At zero current there is no finite voltage-drop length limit in this model.

Optional distributed-load estimate

For N equal-current devices equally spaced at L/N, 2L/N, …, L, each segment carries the current of the devices downstream. Summing those segment drops gives:

ΔVdistributed = (2 × r × L / 1,000) × (I / N²) × (1 + 2 + … + N) = ΔVlumped × (N + 1) / (2N)

The maximum length is Lₘₐₓ from the lumped formula divided by (N + 1)/(2N). One device gives the lumped result; ten give 55% of the lumped drop. The factor approaches one-half as N increases, but simply halving the drop is inaccurate for a small device count.

This is our algebraic derivation from the segment-current method described in Potter's Advanced Fire Training Manual, section 7. The optional estimate assumes equal currents and equal spacing; use an actual segment-by-segment design for different spacing, mixed currents, or branches.

Worked example

For 14 AWG solid uncoated copper, a 300 ft one-way run, and 1.5 A total load, the calculated resistance at 75 °C is approximately 3.071293 Ω/1,000 ft. The loop resistance is 2 × 300 × 3.071293 ÷ 1,000 = 1.842776 Ω. Drop is 1.5 × 1.842776 = 2.764164 V.

At a 24 V source, the last device receives approximately 21.236 V, an 11.517% drop, which passes an entered 16 V minimum. Maximum one-way length is approximately 868.255 ft. At a 20.4 V battery-condition source, the same load leaves 17.636 V at the last device and limits length to approximately 477.540 ft.

For ten equal-current devices evenly spaced over that same 300 ft, the optional estimate gives 2.764164 × 11/20 = 1.520290 V drop. These are fictional calculation inputs, not an equipment specification or exam question.

Copper reference data at 75 °C

Calculated from NBS Handbook 100, Copper Wire Tables: ρ₂₀ = 1/58 Ω·mm²/m and α₂₀ = 0.00393/°C (appendix 5, printed p. 40); AWG geometry (§2.2, p. 6); stranded allowance (appendix 4, p. 38).

d(mm) = 0.127 × 92^((36 − AWG)/39); A = πd²/4; r₂₀ = ρ₂₀ × 304.8/A; r₇₅ = r₂₀ × [1 + 0.00393 × (75 − 20)].

Multiply by 1.02 for the handbook's concentric-lay stranded estimate. These calculated values use ideal annealed, uncoated copper; they are not a cable manufacturer's maximum resistance specification. Actual stranding, tolerances and construction can change resistance. Confirm against your cable's published data. The 75 °C assumption does not establish cable suitability.

Calculated DC resistance, Ω per 1,000 ft of one conductor at 75 °C
AWGSolidStranded estimate
187.76517.9204
164.88354.9812
143.07133.1327
121.93161.9702
101.21481.2391

Table values are rounded for display; calculations retain full precision. No NEC Chapter 9 table data is used.

Design assumptions and limits

The editable 20.4 V battery check is a common design assumption illustrated in Potter's section 7. Confirm it for your equipment and end-of-discharge condition. This tool subtracts cable loss only; enter the available NAC terminal voltage after any internal panel losses. A 24 V nominal source is not a worst-case supply guarantee.

The lumped result is conservative for placement of the entered fixed current on the stated radial run. It does not account for voltage-dependent current, inrush, synchronization modules, connection losses, power-supply regulation, return-fed Class A operation, or additional branches. Use the device's listed maximum current for the applicable settings and waveform.

Check against your project's specifications and the AHJ / your procedure. A pass means only that this simplified voltage estimate meets your entered minimum. Confirm circuit current limits, maximum device voltage, conductor suitability, equipment compatibility, manufacturer instructions and the required design method separately.

Published sources

Preparing for NICET Fire Alarm Systems Level II?

Use the free diagnostic to see which exam domains need more study.

Take the free NICET FA II diagnostic

Read the Level II exam guide

Add this calculator to your site

Copy this HTML into your page. Keep the attribution link. The frame scrolls to show the full calculator and explanation; no external script is needed.

Report an error · Back to Alarm Ladder