Fire alarm standby battery calculator, with the method explained

Estimate the amp-hour capacity needed for a panel and its connected devices during standby followed by alarm. Enter your project's loads, durations and design margin; the tool shows each step.

Draft Pending expert review.

Drafted by the TrueGrade Prep editorial team. Method source checked 17 October 2026.

Enter your battery loads

Results update as you type. All starting currents are fictional examples. Replace them with your equipment's published battery-load currents for the applicable settings. 1 mA = 0.001 A.

Alarm current means the total draw during alarm, including anything still energized in standby. Do not enter only the increase over standby, or count a load in both the panel and device rows.

Device list

Enter per-device currents. Quantity multiplies both currents. Zero quantity excludes a row; remove all rows for a panel-only calculation.

Device group 1
Device group 2
Required durations: set these from your project's specs and the AHJ

24 h standby and 5 min alarm are common design inputs, not quoted requirements. Confirm the durations for your system and the code edition your authority having jurisdiction (AHJ) enforces.

The editable 20% margin is a designer's choice, added to calculated Ah. It is not a universal requirement or a direct battery efficiency percentage. Confirm your project's method and manufacturer instructions.

Tool limits, not equipment ratings: 100 device groups, 0–10,000 devices per group, 0–100 A per current input, 0–1,000 h standby, 0–1,440 min alarm, and 0–1,000% margin.

Calculated results

Total standby current
0.3 A
Total alarm current
1.5 A
Standby capacity
7.2 Ah
Alarm capacity
0.125 Ah
Required capacity before margin
7.325 Ah
Required capacity after 20% margin
8.79 Ah
Next common battery size up
12 Ah

Typical sealed lead-acid sizes considered: 7, 12, 18, 26, 33, 40, 55, 100 Ah. Selects the smallest listed size at or above the unrounded requirement. Display values are rounded to six decimal places.

Capacity estimate only. This does not establish code compliance or panel compatibility. Check charger limits, enclosure capacity, battery voltage, temperature, aging, discharge rating and the manufacturer's approved battery sizes.

How the battery calculation works

Multiply each device's current by its quantity. Add those loads to the panel's current separately for standby and alarm. Use amperes (A), not milliamperes: divide mA by 1,000 to get A. Alarm currents must include the complete alarm-state load, not just the increase above standby.

  • Total standby current: Iₛ = panel standby A + Σ(quantity × per-device standby A).
  • Total alarm current: Iₐ = panel alarm A + Σ(quantity × per-device alarm A).
  • Standby Ah = Iₛ × standby hours.
  • Alarm Ah = Iₐ × (alarm minutes / 60).
  • Required Ah before margin = standby Ah + alarm Ah.
  • Required Ah after margin = required Ah before margin × (1 + margin % / 100).

Ah = [I_standby × hours + I_alarm × (minutes / 60)] × (1 + margin)

In the compact formula, margin is a decimal: enter 20% in the calculator to use 0.20 in the equation. Choose the smallest listed battery capacity at least as large as the unrounded final result.

This current-times-duration method is described in Potter's Advanced Fire Training Manual, Battery Standby Calculations, printed page 7-53. Its example uses a 1.2 multiplier. Here the margin is editable so the designer can choose the value appropriate to the project.

Worked example

These fictional loads match the starting inputs; they are not equipment specifications or an exam question. A panel draws 0.20 A in standby and 0.30 A in alarm. Twenty detectors each draw 0.005 A in standby and 0.010 A in alarm. Ten notification appliances each draw 0 A in standby and 0.10 A in alarm.

  • Standby current = 0.20 + (20 × 0.005) + (10 × 0) = 0.30 A.
  • Alarm current = 0.30 + (20 × 0.010) + (10 × 0.10) = 1.50 A.
  • At 24 h standby: 0.30 × 24 = 7.20 Ah.
  • At 5 min alarm: 1.50 × (5 / 60) = 0.125 Ah.
  • Before margin: 7.20 + 0.125 = 7.325 Ah.
  • With a chosen 20% margin: 7.325 × 1.20 = 8.79 Ah.
  • Next listed typical size: 12 Ah, subject to equipment compatibility checks.

Durations and margin are project inputs

Set these from your project's specs and the AHJ. The editable 24 h and 5 min defaults are common design inputs, not quoted requirements. NFPA 72 sets secondary-power duration requirements; check your own licensed copy of the edition your AHJ enforces for the applicable system and conditions. No code-book text or tables are reproduced here. NFPA provides code information and free read-only access.

The 20% default is a designer's choice. An additive margin is different from an efficiency derating: adding 20% multiplies by 1.20, while allowing for 80% usable capacity divides by 0.80, equivalent to a 25% additive margin. Follow the factor and method specified for your equipment; this tool does not automatically apply a separate aging or temperature factor.

Typical sizes and design limits

The comparison list is 7, 12, 18, 26, 33, 40, 55 and 100 Ah, typical sealed lead-acid sizes. It is a convenience list, not a manufacturer's approved battery schedule. Other sizes exist. A result over 100 Ah returns no listed size; the calculator never rounds it down to 100 Ah.

Capacity is the bank's Ah rating at the required system voltage. For two equal 12 V batteries connected in series for 24 V, voltage adds while Ah stays the same: two 12 V, 12 Ah batteries form a 24 V, 12 Ah bank, not 24 Ah. Use the manufacturer's approved battery arrangement.

Check against your project's specifications and the AHJ / your procedure. This simplified estimate assumes constant current in each operating period. Confirm equipment compatibility, charger capacity and recharge time, enclosure limits, temperature, battery aging, discharge-rate rating, end-of-discharge voltage and manufacturer instructions. Check voltage drop separately. Account for modules, annunciators and auxiliary loads on their actual supplying battery bank; calculate separate supplies separately.

The displayed size is a capacity comparison, not a code-compliance verdict or approval to install a battery.

Published method source

Potter Electric Signal Company. Advanced Fire Training Manual, 8700055, Rev H (May 2017), Battery Standby Calculations, printed page 7-53 (PDF page 57). Checked 17 October 2026. Used for the amp-hour method and series-bank explanation, not as a source of current code requirements or a universal margin.

Preparing for NICET Fire Alarm Systems Level II?

Use the free diagnostic to see which exam domains need more study.

Take the free NICET FA II diagnostic

Read the Level II exam guide